Modeled Line Rating Forecasts
Hourly, vintage-stamped screening estimates for mapped transmission lines across every supported US grid.
Overview
Each row joins a public line-map snapshot to route-sampled forecast weather, a published owner or regional assumption profile, the validation margin, model version, and materialization run. The result is a temperature-adjusted IEEE 738 conductor estimate capped at an equipment floor fitted to ERCOT's submitted temperature/rating tables; it is not an operator facility rating or transfer limit because the public map does not provide the actual conductor, clearance, relay, transformer, or terminal-equipment limits of any facility.
Query contract
Analysis rules
Related analysis
Interpretation
Access
Need the full history of this dataset in Snowflake, Databricks or your own storage? Data services delivers it on a schedule.
Schema41
valid_timeDateTime64(6, 'UTC')forecast_as_ofDateTime64(6, 'UTC')line_snapshot_timeDateTime64(6, 'UTC')isoLowCardinality(String)line_idLowCardinality(String)line_nameNullable(String)voltage_kvNullable(Float64)methodLowCardinality(String)model_versionLowCardinality(String)rating_ratioFloat64rating_change_pctFloat64ambient_temp_cNullable(Float64)temperature_guardband_cNullable(Float64)applied_wind_msNullable(Float64)applied_wind_angle_degNullable(Float64)applied_solar_wm2Nullable(Float64)applied_pressure_paNullable(Float64)observed_wind_msNullable(Float64)observed_wind_angle_degNullable(Float64)observed_solar_wm2Nullable(Float64)observed_pressure_paNullable(Float64)bearing_degNullable(Float64)limiting_lonNullable(Float64)limiting_latNullable(Float64)sample_countNullable(Int32)weather_fallback_sample_countNullable(Int32)assumption_profileLowCardinality(String)assumption_providerLowCardinality(String)assumption_sourceStringreference_ambient_temp_cFloat64reference_wind_msFloat64reference_wind_angle_degFloat64reference_solar_wm2Float64max_conductor_temp_cFloat64ambient_floor_cNullable(Float64)floor_appliedNullable(Bool)representative_voltage_kvInt32conductor_diameter_mFloat64weather_sourceLowCardinality(String)run_idStringingested_atDateTime64(6, 'UTC')Sample data
| valid_time | forecast_as_of | line_snapshot_time | iso | line_id | line_name | voltage_kv | method | model_version | rating_ratio | rating_change_pct | ambient_temp_c | temperature_guardband_c | applied_wind_ms | applied_wind_angle_deg | applied_solar_wm2 | applied_pressure_pa | observed_wind_ms | observed_wind_angle_deg | observed_solar_wm2 | observed_pressure_pa | bearing_deg | limiting_lon | limiting_lat | sample_count | weather_fallback_sample_count | assumption_profile | assumption_provider | assumption_source | reference_ambient_temp_c | reference_wind_ms | reference_wind_angle_deg | reference_solar_wm2 | max_conductor_temp_c | ambient_floor_c | floor_applied | representative_voltage_kv | conductor_diameter_m | weather_source | run_id | ingested_at |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 2026-10-19 09:00:00.000000 | 2026-10-16 08:45:03.967953 | 2026-10-15 01:57:21.000000 | ERCOT | grid-line-15ec49bba1193369 | Moffat Substation → Lake Belton Substation | 138 | ambient_adjusted | ieee738-hrrr-v3 | 1 | 0 | 12.2487 | 0 | 0.8931 | 60 | 1000 | 101325 | 2.2627 | 129.6613 | 0 | 101325 | 14.3436 | -97.43391 | 31.141412 | 2 | 0 | ercot-regional-public | ERCOT regional default (AEP Texas table) | https://github.com/NREL/DynamicLineRatings/blob/d8e443eb09e428fb0fc8452370fd72fe8819f927/data/regional_assumptions.csv | 20 | 0.8931 | 60 | 1000 | 85 | 24.5 | true | 115 | 0.0277 | public_forecast_fallback | d13f24d6-758a-46fe-9692-8004e05b7181 | 2026-10-16 10:41:47.391025 |
| 2026-10-19 09:00:00.000000 | 2026-10-16 08:45:03.967953 | 2026-10-15 01:57:21.000000 | ERCOT | grid-line-15d6d39d4160a82b | Sand Lake Switching Station transmission line | 138 | ambient_adjusted | ieee738-hrrr-v3 | 1 | 0 | 14.3349 | 0 | 0.6096 | 90 | 1023.91 | 101325 | 4.3211 | 108.6491 | 0 | 101325 | 131.4325 | -103.463804 | 31.509235 | 2 | 0 | ercot-txued-public | TXUED | https://github.com/NREL/DynamicLineRatings/blob/d8e443eb09e428fb0fc8452370fd72fe8819f927/data/regional_assumptions.csv | 20 | 0.6096 | 90 | 1023.91 | 90 | 21.5 | true | 115 | 0.0277 | public_forecast_fallback | d13f24d6-758a-46fe-9692-8004e05b7181 | 2026-10-16 10:41:47.391025 |
| 2026-10-19 09:00:00.000000 | 2026-10-16 08:45:03.967953 | 2026-10-15 01:57:21.000000 | ERCOT | grid-line-156b9a5fc3afad2e | Ballinger Substation transmission line | 69 | ambient_adjusted | ieee738-hrrr-v3 | 1 | 0 | 11.681 | 0 | 0.8931 | 60 | 1000 | 101325 | 3.2916 | 144.1925 | 0 | 101325 | -121.7185 | -99.944411 | 31.74294 | 2 | 0 | ercot-regional-public | ERCOT regional default (AEP Texas table) | https://github.com/NREL/DynamicLineRatings/blob/d8e443eb09e428fb0fc8452370fd72fe8819f927/data/regional_assumptions.csv | 20 | 0.8931 | 60 | 1000 | 85 | 24.5 | true | 69 | 0.0183 | public_forecast_fallback | d13f24d6-758a-46fe-9692-8004e05b7181 | 2026-10-16 10:41:47.391025 |
| 2026-10-19 09:00:00.000000 | 2026-10-16 08:45:03.967953 | 2026-10-15 01:57:21.000000 | ERCOT | grid-line-15692d9f4b8f16ac | Calvert Substation transmission line | 69 | ambient_adjusted | ieee738-hrrr-v3 | 1 | 0 | 12.1212 | 0 | 0.8931 | 60 | 1000 | 101325 | 2.1154 | 124.3428 | 0 | 101325 | -83.6277 | -96.916298 | 31.022178 | 2 | 0 | ercot-regional-public | ERCOT regional default (AEP Texas table) | https://github.com/NREL/DynamicLineRatings/blob/d8e443eb09e428fb0fc8452370fd72fe8819f927/data/regional_assumptions.csv | 20 | 0.8931 | 60 | 1000 | 85 | 24.5 | true | 69 | 0.0183 | public_forecast_fallback | d13f24d6-758a-46fe-9692-8004e05b7181 | 2026-10-16 10:41:47.391025 |
| 2026-10-19 09:00:00.000000 | 2026-10-16 08:45:03.967953 | 2026-10-15 01:57:21.000000 | ERCOT | grid-line-151643aba35fcb30 | Salem Substation → Colorado City Substation | 138 | ambient_adjusted | ieee738-hrrr-v3 | 1 | 0 | 12.2494 | 0 | 0.8931 | 60 | 1000 | 101325 | 3.8639 | 161.6067 | 0 | 101325 | -104.2513 | -101.086402 | 32.390294 | 4 | 0 | ercot-regional-public | ERCOT regional default (AEP Texas table) | https://github.com/NREL/DynamicLineRatings/blob/d8e443eb09e428fb0fc8452370fd72fe8819f927/data/regional_assumptions.csv | 20 | 0.8931 | 60 | 1000 | 85 | 24.5 | true | 115 | 0.0277 | public_forecast_fallback | d13f24d6-758a-46fe-9692-8004e05b7181 | 2026-10-16 10:41:47.391025 |
| 2026-10-19 09:00:00.000000 | 2026-10-16 08:45:03.967953 | 2026-10-15 01:57:21.000000 | ERCOT | grid-line-14f2d5140b154e57 | Westbrook Substation transmission line | 69 | ambient_adjusted | ieee738-hrrr-v3 | 1 | 0 | 12.3167 | 0 | 0.8931 | 60 | 1000 | 101325 | 3.8515 | 159.508 | 0 | 101325 | -102.8474 | -101.014324 | 32.360148 | 2 | 0 | ercot-regional-public | ERCOT regional default (AEP Texas table) | https://github.com/NREL/DynamicLineRatings/blob/d8e443eb09e428fb0fc8452370fd72fe8819f927/data/regional_assumptions.csv | 20 | 0.8931 | 60 | 1000 | 85 | 24.5 | true | 69 | 0.0183 | public_forecast_fallback | d13f24d6-758a-46fe-9692-8004e05b7181 | 2026-10-16 10:41:47.391025 |
| 2026-10-19 09:00:00.000000 | 2026-10-16 08:45:03.967953 | 2026-10-15 01:57:21.000000 | ERCOT | grid-line-14d6bb22ce0638e2 | Worsham Field Substation transmission line | 138 | ambient_adjusted | ieee738-hrrr-v3 | 1 | 0 | 14.7842 | 0 | 0.6096 | 90 | 913.67 | 101325 | 3.731 | 124.7242 | 0 | 101325 | 15.957 | -103.334106 | 31.356312 | 2 | 0 | ercot-tnp-public | TNP | https://github.com/NREL/DynamicLineRatings/blob/d8e443eb09e428fb0fc8452370fd72fe8819f927/data/regional_assumptions.csv | 20 | 0.6096 | 90 | 913.67 | 67.5 | 24.5 | true | 115 | 0.0277 | public_forecast_fallback | d13f24d6-758a-46fe-9692-8004e05b7181 | 2026-10-16 10:41:47.391025 |
| 2026-10-19 09:00:00.000000 | 2026-10-16 08:45:03.967953 | 2026-10-15 01:57:21.000000 | ERCOT | grid-line-14460f91f203f300 | 69 kV transmission line | 69 | ambient_adjusted | ieee738-hrrr-v3 | 1 | 0 | 11.5805 | 0 | 0.8931 | 60 | 1000 | 101325 | 2.866 | 119.7735 | 0 | 101325 | -122.7479 | -96.398972 | 33.292106 | 2 | 0 | ercot-regional-public | ERCOT regional default (AEP Texas table) | https://github.com/NREL/DynamicLineRatings/blob/d8e443eb09e428fb0fc8452370fd72fe8819f927/data/regional_assumptions.csv | 20 | 0.8931 | 60 | 1000 | 85 | 24.5 | true | 69 | 0.0183 | public_forecast_fallback | d13f24d6-758a-46fe-9692-8004e05b7181 | 2026-10-16 10:41:47.391025 |
| 2026-10-19 09:00:00.000000 | 2026-10-16 08:45:03.967953 | 2026-10-15 01:57:21.000000 | ERCOT | grid-line-143e253005ff87d7 | Midessa Substation → Midland West Substation | 138 | ambient_adjusted | ieee738-hrrr-v3 | 1 | 0 | 11.7615 | 0 | 0.8931 | 60 | 1000 | 101325 | 3.8897 | 154.831 | 0 | 101325 | -130.1437 | -102.175633 | 31.967124 | 2 | 0 | ercot-regional-public | ERCOT regional default (AEP Texas table) | https://github.com/NREL/DynamicLineRatings/blob/d8e443eb09e428fb0fc8452370fd72fe8819f927/data/regional_assumptions.csv | 20 | 0.8931 | 60 | 1000 | 85 | 24.5 | true | 115 | 0.0277 | public_forecast_fallback | d13f24d6-758a-46fe-9692-8004e05b7181 | 2026-10-16 10:41:47.391025 |
| 2026-10-19 09:00:00.000000 | 2026-10-16 08:45:03.967953 | 2026-10-15 01:57:21.000000 | ERCOT | grid-line-1432bc903dda94f3 | Midkiff Switching Station transmission line | 69 | ambient_adjusted | ieee738-hrrr-v3 | 1 | 0 | 12.0214 | 0 | 0.8931 | 60 | 1000 | 101325 | 4.5924 | 151.1367 | 0 | 101325 | 39.3435 | -101.807018 | 31.521343 | 2 | 0 | ercot-regional-public | ERCOT regional default (AEP Texas table) | https://github.com/NREL/DynamicLineRatings/blob/d8e443eb09e428fb0fc8452370fd72fe8819f927/data/regional_assumptions.csv | 20 | 0.8931 | 60 | 1000 | 85 | 24.5 | true | 69 | 0.0183 | public_forecast_fallback | d13f24d6-758a-46fe-9692-8004e05b7181 | 2026-10-16 10:41:47.391025 |
| 2026-10-19 09:00:00.000000 | 2026-10-16 08:45:03.967953 | 2026-10-15 01:57:21.000000 | ERCOT | grid-line-1405c568ff1b5b97 | Victoria Switching Station → Dupont Switching Station | 138 | ambient_adjusted | ieee738-hrrr-v3 | 1 | 0 | 15.7335 | 0 | 0.8931 | 60 | 1000 | 101325 | 3.0351 | 56.5549 | 0 | 101325 | 163.3971 | -96.945905 | 28.693523 | 2 | 0 | ercot-regional-public | ERCOT regional default (AEP Texas table) | https://github.com/NREL/DynamicLineRatings/blob/d8e443eb09e428fb0fc8452370fd72fe8819f927/data/regional_assumptions.csv | 20 | 0.8931 | 60 | 1000 | 85 | 24.5 | true | 115 | 0.0277 | public_forecast_fallback | d13f24d6-758a-46fe-9692-8004e05b7181 | 2026-10-16 10:41:47.391025 |
| 2026-10-19 09:00:00.000000 | 2026-10-16 08:45:03.967953 | 2026-10-15 01:57:21.000000 | ERCOT | grid-line-13e9de761a238d48 | South Midland Substation transmission line | 138 | ambient_adjusted | ieee738-hrrr-v3 | 1 | 0 | 11.6787 | 0 | 0.8931 | 60 | 1000 | 101325 | 3.8714 | 156.4848 | 0 | 101325 | -12.6954 | -102.010851 | 31.939921 | 2 | 0 | ercot-regional-public | ERCOT regional default (AEP Texas table) | https://github.com/NREL/DynamicLineRatings/blob/d8e443eb09e428fb0fc8452370fd72fe8819f927/data/regional_assumptions.csv | 20 | 0.8931 | 60 | 1000 | 85 | 24.5 | true | 115 | 0.0277 | public_forecast_fallback | d13f24d6-758a-46fe-9692-8004e05b7181 | 2026-10-16 10:41:47.391025 |
| 2026-10-19 09:00:00.000000 | 2026-10-16 08:45:03.967953 | 2026-10-15 01:57:21.000000 | ERCOT | grid-line-13cd1a89ad5debc5 | Big Foot Substation → Pleasanton Substation | 138 | ambient_adjusted | ieee738-hrrr-v3 | 1 | 0 | 16.1236 | 0 | 0.8931 | 60 | 1000 | 101325 | 2.7969 | 90.0708 | 0 | 101325 | -88.2705 | -98.484927 | 28.948294 | 5 | 0 | ercot-regional-public | ERCOT regional default (AEP Texas table) | https://github.com/NREL/DynamicLineRatings/blob/d8e443eb09e428fb0fc8452370fd72fe8819f927/data/regional_assumptions.csv | 20 | 0.8931 | 60 | 1000 | 85 | 24.5 | true | 115 | 0.0277 | public_forecast_fallback | d13f24d6-758a-46fe-9692-8004e05b7181 | 2026-10-16 10:41:47.391025 |
| 2026-10-19 09:00:00.000000 | 2026-10-16 08:45:03.967953 | 2026-10-15 01:57:21.000000 | ERCOT | grid-line-1355142806c9b5c5 | Stratton Substation → Bunsen Substation | 138 | ambient_adjusted | ieee738-hrrr-v3 | 1 | 0 | 20.369 | 0 | 0.8931 | 60 | 1000 | 101325 | 2.9128 | 19.9417 | 0 | 101325 | -164.9707 | -97.879364 | 27.621935 | 2 | 0 | ercot-regional-public | ERCOT regional default (AEP Texas table) | https://github.com/NREL/DynamicLineRatings/blob/d8e443eb09e428fb0fc8452370fd72fe8819f927/data/regional_assumptions.csv | 20 | 0.8931 | 60 | 1000 | 85 | 24.5 | true | 115 | 0.0277 | public_forecast_fallback | d13f24d6-758a-46fe-9692-8004e05b7181 | 2026-10-16 10:41:47.391025 |
| 2026-10-19 09:00:00.000000 | 2026-10-16 08:45:03.967953 | 2026-10-15 01:57:21.000000 | ERCOT | grid-line-134e507bd857c76f | 69 kV transmission line | 69 | ambient_adjusted | ieee738-hrrr-v3 | 1 | 0 | 11.2108 | 0 | 0.8931 | 60 | 1000 | 101325 | 3.8222 | 161.9685 | 0 | 101325 | 90.353 | -98.361086 | 33.496425 | 2 | 0 | ercot-regional-public | ERCOT regional default (AEP Texas table) | https://github.com/NREL/DynamicLineRatings/blob/d8e443eb09e428fb0fc8452370fd72fe8819f927/data/regional_assumptions.csv | 20 | 0.8931 | 60 | 1000 | 85 | 24.5 | true | 69 | 0.0183 | public_forecast_fallback | d13f24d6-758a-46fe-9692-8004e05b7181 | 2026-10-16 10:41:47.391025 |
| 2026-10-19 09:00:00.000000 | 2026-10-16 08:45:03.967953 | 2026-10-15 01:57:21.000000 | ERCOT | grid-line-0e2fc9e543736247 | 69 kV transmission line | 69 | ambient_adjusted | ieee738-hrrr-v3 | 1 | 0 | 11.4309 | 0 | 0.8931 | 60 | 1000 | 101325 | 3.7307 | 153.452 | 0 | 101325 | 132.0394 | -97.824115 | 33.606875 | 2 | 0 | ercot-regional-public | ERCOT regional default (AEP Texas table) | https://github.com/NREL/DynamicLineRatings/blob/d8e443eb09e428fb0fc8452370fd72fe8819f927/data/regional_assumptions.csv | 20 | 0.8931 | 60 | 1000 | 85 | 24.5 | true | 69 | 0.0183 | public_forecast_fallback | d13f24d6-758a-46fe-9692-8004e05b7181 | 2026-10-16 10:41:47.391025 |
| 2026-10-19 09:00:00.000000 | 2026-10-16 08:45:03.967953 | 2026-10-15 01:57:21.000000 | ERCOT | grid-line-12e4037f31536539 | Greens Bayou 69kV Substation → Channelview Substation | 69 | ambient_adjusted | ieee738-hrrr-v3 | 1 | 0 | 18.9552 | 0 | 0.6096 | 90 | 794.93 | 101325 | 2.9953 | 58.5059 | 0 | 101325 | -118.8386 | -95.152424 | 29.775387 | 2 | 0 | ercot-centerpoint-public | CenterPoint | https://github.com/NREL/DynamicLineRatings/blob/d8e443eb09e428fb0fc8452370fd72fe8819f927/data/regional_assumptions.csv | 20 | 0.6096 | 90 | 794.93 | 75 | 32.5 | true | 69 | 0.0183 | public_forecast_fallback | d13f24d6-758a-46fe-9692-8004e05b7181 | 2026-10-16 10:41:47.391025 |
| 2026-10-19 09:00:00.000000 | 2026-10-16 08:45:03.967953 | 2026-10-15 01:57:21.000000 | ERCOT | grid-line-1257dfe6ef4f54d5 | Smith Substation → Stevens Substation | 69 | ambient_adjusted | ieee738-hrrr-v3 | 1 | 0 | 20.1089 | 0 | 0.8931 | 60 | 1000 | 101325 | 3.4385 | 35.5981 | 0 | 101325 | -11.0318 | -97.619507 | 27.86021 | 2 | 0 | ercot-regional-public | ERCOT regional default (AEP Texas table) | https://github.com/NREL/DynamicLineRatings/blob/d8e443eb09e428fb0fc8452370fd72fe8819f927/data/regional_assumptions.csv | 20 | 0.8931 | 60 | 1000 | 85 | 24.5 | true | 69 | 0.0183 | public_forecast_fallback | d13f24d6-758a-46fe-9692-8004e05b7181 | 2026-10-16 10:41:47.391025 |
| 2026-10-19 09:00:00.000000 | 2026-10-16 08:45:03.967953 | 2026-10-15 01:57:21.000000 | ERCOT | grid-line-124e37a9f250bef6 | Temple South Substation → Scott and White Substation | 138 | ambient_adjusted | ieee738-hrrr-v3 | 1 | 0 | 12.3046 | 0 | 0.8931 | 60 | 1000 | 101325 | 2.0746 | 127.6345 | 0 | 101325 | 18.2933 | -97.361236 | 31.074655 | 2 | 0 | ercot-regional-public | ERCOT regional default (AEP Texas table) | https://github.com/NREL/DynamicLineRatings/blob/d8e443eb09e428fb0fc8452370fd72fe8819f927/data/regional_assumptions.csv | 20 | 0.8931 | 60 | 1000 | 85 | 24.5 | true | 115 | 0.0277 | public_forecast_fallback | d13f24d6-758a-46fe-9692-8004e05b7181 | 2026-10-16 10:41:47.391025 |
| 2026-10-19 09:00:00.000000 | 2026-10-16 08:45:03.967953 | 2026-10-15 01:57:21.000000 | ERCOT | grid-line-11a0a15b95136d4a | 138 kV transmission line | 138 | ambient_adjusted | ieee738-hrrr-v3 | 1 | 0 | 10.4106 | 0 | 0.8931 | 60 | 1000 | 101325 | 2.5544 | 122.5997 | 0 | 101325 | 28.9062 | -95.694122 | 32.962301 | 2 | 0 | ercot-regional-public | ERCOT regional default (AEP Texas table) | https://github.com/NREL/DynamicLineRatings/blob/d8e443eb09e428fb0fc8452370fd72fe8819f927/data/regional_assumptions.csv | 20 | 0.8931 | 60 | 1000 | 85 | 24.5 | true | 115 | 0.0277 | public_forecast_fallback | d13f24d6-758a-46fe-9692-8004e05b7181 | 2026-10-16 10:41:47.391025 |
| 2026-10-19 09:00:00.000000 | 2026-10-16 08:45:03.967953 | 2026-10-15 01:57:21.000000 | ERCOT | grid-line-130c311b569f4a79 | 138 kV transmission line | 138 | ambient_adjusted | ieee738-hrrr-v3 | 1 | 0 | 17.4591 | 0 | 0.8931 | 60 | 1000 | 101325 | 2.7076 | 54.4585 | 0 | 101325 | -100.938 | -94.923705 | 29.845583 | 2 | 0 | ercot-regional-public | ERCOT regional default (AEP Texas table) | https://github.com/NREL/DynamicLineRatings/blob/d8e443eb09e428fb0fc8452370fd72fe8819f927/data/regional_assumptions.csv | 20 | 0.8931 | 60 | 1000 | 85 | 24.5 | true | 115 | 0.0277 | public_forecast_fallback | d13f24d6-758a-46fe-9692-8004e05b7181 | 2026-10-16 10:41:47.391025 |
| 2026-10-19 09:00:00.000000 | 2026-10-16 08:45:03.967953 | 2026-10-15 01:57:21.000000 | ERCOT | grid-line-0ff7f0c89a413ab4 | Red Bluff Substation → Danevang Substation | 138 | ambient_adjusted | ieee738-hrrr-v3 | 1 | 0 | 15.4437 | 0 | 0.8931 | 60 | 1000 | 101325 | 2.8662 | 58.6308 | 0 | 101325 | 179.0804 | -96.524826 | 28.886072 | 4 | 0 | ercot-regional-public | ERCOT regional default (AEP Texas table) | https://github.com/NREL/DynamicLineRatings/blob/d8e443eb09e428fb0fc8452370fd72fe8819f927/data/regional_assumptions.csv | 20 | 0.8931 | 60 | 1000 | 85 | 24.5 | true | 115 | 0.0277 | public_forecast_fallback | d13f24d6-758a-46fe-9692-8004e05b7181 | 2026-10-16 10:41:47.391025 |
| 2026-10-19 09:00:00.000000 | 2026-10-16 08:45:03.967953 | 2026-10-15 01:57:21.000000 | ERCOT | grid-line-10b902e0341f77eb | Sulphur Springs Switching Station transmission line | 138 | ambient_adjusted | ieee738-hrrr-v3 | 1 | 0 | 10.3008 | 0 | 0.8931 | 60 | 1000 | 101325 | 2.4986 | 125.2799 | 0 | 101325 | -159.233 | -95.615649 | 33.085302 | 2 | 0 | ercot-regional-public | ERCOT regional default (AEP Texas table) | https://github.com/NREL/DynamicLineRatings/blob/d8e443eb09e428fb0fc8452370fd72fe8819f927/data/regional_assumptions.csv | 20 | 0.8931 | 60 | 1000 | 85 | 24.5 | true | 115 | 0.0277 | public_forecast_fallback | d13f24d6-758a-46fe-9692-8004e05b7181 | 2026-10-16 10:41:47.391025 |
| 2026-10-19 09:00:00.000000 | 2026-10-16 08:45:03.967953 | 2026-10-15 01:57:21.000000 | ERCOT | grid-line-109c3d1c0067a7ff | Andrews County South Switching Station transmission line | 345 | ambient_adjusted | ieee738-hrrr-v3 | 1 | 0 | 11.9037 | 0 | 0.8931 | 60 | 1000 | 101325 | 4.3111 | 149.7607 | 0 | 101325 | 156.5556 | -102.840469 | 32.287486 | 2 | 0 | ercot-regional-public | ERCOT regional default (AEP Texas table) | https://github.com/NREL/DynamicLineRatings/blob/d8e443eb09e428fb0fc8452370fd72fe8819f927/data/regional_assumptions.csv | 20 | 0.8931 | 60 | 1000 | 85 | 24.5 | true | 345 | 0.0304 | public_forecast_fallback | d13f24d6-758a-46fe-9692-8004e05b7181 | 2026-10-16 10:41:47.391025 |
| 2026-10-19 09:00:00.000000 | 2026-10-16 08:45:03.967953 | 2026-10-15 01:57:21.000000 | ERCOT | grid-line-1031f57baa9340ad | Central Bluff Substation transmission line | 345 | ambient_adjusted | ieee738-hrrr-v3 | 1 | 0 | 10.6689 | 0 | 0.8931 | 60 | 1000 | 101325 | 3.1873 | 163.597 | 0 | 101325 | 158.3465 | -100.167048 | 32.10138 | 2 | 0 | ercot-regional-public | ERCOT regional default (AEP Texas table) | https://github.com/NREL/DynamicLineRatings/blob/d8e443eb09e428fb0fc8452370fd72fe8819f927/data/regional_assumptions.csv | 20 | 0.8931 | 60 | 1000 | 85 | 24.5 | true | 345 | 0.0304 | public_forecast_fallback | d13f24d6-758a-46fe-9692-8004e05b7181 | 2026-10-16 10:41:47.391025 |